Air conditioner leaking water inside: what it means and what to check
Maintenance

Air conditioner leaking water inside: what it means and what to check

Published 6 min read

A drain line needs a fall of at least 1 in 100, 10 mm per metre, to carry away the water a unit pulls out of humid Sydney air. Here is what a drip inside means, in the order a technician checks it, and the three things to try first.

Where the water comes from

Cross-section of a wall split: moist room air crosses the cold coil, the water it sheds collects in the tray and leaves through the drain hose to the outside.outsidetraymoist room aircooler, drier airdrain hose
Room air crosses the cold coil and leaves its moisture behind. The water collects in the tray under the coil and runs out through the drain hose to the outside. A drip from the front of the unit means that path is blocked, not that the unit is broken.

An air conditioner on cool is a dehumidifier as much as a cooler. Room air passes over a coil cold enough for the moisture in it to condense, the way a cold glass sweats, and that water collects in a tray under the coil and runs out through a drain hose. On a muggy Sydney afternoon that is a steady trickle: the Bureau's Richmond station averages 47 percent humidity at 3pm in summer, and the coast is stickier still.

So water dripping from the front of the indoor unit does not mean the unit is broken. It means the water it made has stopped going where it should. That is a drain problem, a tray problem or, less often, a refrigerant problem, and a technician checks them in that order because the first is common and usually a quick fix.

Three things to check before you call

The manufacturers' own manuals, which we keep on our manuals and brochures page, agree on the first checks. Mitsubishi Electric's MSZ-EF user manual lists two: is the front panel closed properly, and does water flow freely from the end of the drain hose outside? Panasonic's Z Series operating instructions add that the drain pipe must be connected, kept clear of gutters and containers, and not sitting in water, because a hose end under water cannot drain.

The third check is the filters. Mitsubishi Electric's MSZ-AP manual is blunt about it: dirt and dust in the unit can clog the drain passage. Slide the filters out, rinse them, let them dry in the shade and put them back. If the dripping stops, that was the cause.

If it does not, both brands say the same thing: stop using the unit and call. Water leaking from the indoor unit is on the "contact your dealer immediately" list in the Panasonic manual and the "stop using the air conditioner" list in the Mitsubishi Electric one. Running it wet risks the electronics behind the coil and the plaster below it.

Not sure what size you need?Answer five quick questions and get a kW recommendation with matching systems.Size it for me

Cause one: a blocked condensate drain

The drain hose is a narrow tube that carries slightly dirty water through a warm wall cavity, which is ideal for the slime that grows in it. Over a summer the film thickens, dust from a dirty filter adds to it, and one day the tray fills faster than the hose can empty it. On our repairs page the entry reads "water dripping inside: blocked condensate drain or a full tray", and the fix is listed as clear the drain, check the fall on the line, run it and watch it.

The last step matters. A drain that has been cleared but not watched can refill in twenty minutes if the real problem was never the blockage. That is why we run the system on cool after clearing and watch the hose end outside until the water is flowing, rather than packing up when the tray is empty.

Cause two: the fall on the line, and a full tray

Fall the whole way1 in 10010 mm of fall per metreA sag traps waterpockettray backs up
Left: the hose falls the whole way to the outside, 1 in 100 or more (the slope is exaggerated here). Right: a sag lets a pocket of water sit in the low point, flow stops behind it and the tray backs up until it drips over the front.

Condensate drains by gravity, so the hose has to go downhill the whole way. Mitsubishi Electric's PEAD ducted installation manual sets the number: a downward pitch of 1 in 100 or more, which is 10 mm of fall for every metre of run, and it warns that if the unit is hung with the drain side higher, water leakage may result. The same manual tells the installer to hang the unit level with a spirit level, because a tray that tilts the wrong way holds water instead of shedding it.

On a wall-mounted split system the rule is the same and the failure is usually a sag: a hose looped through the wall or dropped into a bend traps a pocket of water, air locks behind it, and the tray backs up. On a ducted system the tray sits in the roof space, and several ranges pair it with a built-in condensate pump to lift the water out. When the pump fails the tray fills and the first sign is a stain on the ceiling under the unit, often nowhere near a grille. This is also where a duct joint sweating in a hot roof can look like a leak: the fix is insulation, not plumbing.

Cause three: a coil that froze

1airflow starved2the coil freezes3thaw floods the tray
A clogged filter or a low refrigerant charge lets the coil drop below freezing. Ice builds while the unit blows weak air, then thaws all at once and puts more water in the tray than it can drain.

The third cause is the one that surprises people. If the coil gets too cold, the moisture on it freezes instead of dripping. The unit blows weak, slightly warm air while the ice builds, then the ice thaws when the system stops and dumps more water at once than the tray was ever meant to hold. Two things make a coil freeze: airflow starved by a clogged filter, which is back to the first check, or a refrigerant charge that has dropped.

A sealed system does not use up refrigerant, so a low charge means a leak somewhere in the pipework, and topping it up without finding the leak sells you the same repair again next summer. We pressure test, trace the leak and quote before anything is fitted. On an older unit running R22 refrigerant a leak is one of the cases where we will quote a replacement alongside the repair, because the gas and the parts are no longer easy to get.

Water outside is usually fine

Dripping from the outdoor unit is normal more often than not. In cool and dry modes the pipes and their connections get cold enough to condense water out of the air, and in heating the outdoor coil is the cold side, so it drips as it defrosts. Mitsubishi Electric's MSZ-EF manual and Panasonic's Z Series instructions both list this under "not a fault".

Two outdoor signs are worth a call. Water running down the wall from the pipe run, which points to a gap in the pipe insulation, and a puddle that appears when the unit is off and the weather is dry, which is not condensate.

What a repair visit covers

Tell us whether it is a split or a ducted system when you book, because they are not the same job: on a split everything is reachable from the wall, on a ducted the tray, the pump and the drain run are in the roof. The diagnosis fee is quoted before we book, the repair is a fixed price you approve before work starts, and a drain clear or a hose rerun is done on the day. Standard repairs are booked within a few business days; if water is coming through a ceiling, our 24/7 emergency repairs service jumps the queue.

Once it is fixed, a yearly maintenance visit that clears the drain and cleans the coil is what keeps it fixed, and if the tray and coil have gone black, a deep clean deals with the slime the drain hose grew from.

Sources

All guides Get a fixed quote